Sensor OS2014

SCAN TRONIC

C O M B U S T I O N O P T I M I Z I N G

Wide band lambda sensor OS2014

 

Wide band Lambda sensor OS2014 is a planar ZrO2 dual cell with integrated heater and is designed to measure the oxygen content value of exhaust gases.

The heater supply voltage is controlled, so the temperature of the sensor is kept at the operation point. During the water condensation phase the heater power is limited to avoid damage to the sensor’s ceramic.

Sensor OS2014 operates in combination with a special developed Oxygen Control OC2016 from Scan Tronic.

 

  • The lambda sensor should be installed at point which permits the measurement of a representative exhaust-gas mixture, which does not exceed the maximum permissible temperature.
  • Install at a point where the gas is as hot as possible.
  • Observe the maximum permissible temperature.
  • As far as possible install the sensor vertically.
  • The sensor is not to be fitted near to the exhaust pipe outlet, so that the influence of the outside air can be ruled out.
  • The exhaust-gas passage opposite the sensor must be free of leaks in order to avoid the effects of leak-air.
  • Protect the sensor against condensation water.

 

Cable lengt

850mm

 

 

Insertion length

29 mm

 

 

Thread

M18x1,5

 

Exhaaust gas pressure

1.5 bar

 

Working temperature:

 

Exhaust gas temperature

 

 

 

max.9000C

Ambient temperature

 

Calibration interval

0 - 600C

 

max.6 months

 

Scan Tronic Aps Contact

Sverigesvej 16 info@scan-tronic.dk

8700 Horsens Phone: +45 21660085

Denmark