Your best partner in the combustion optimization industry and flue gas (oxygen) analyses.
p
Wide band Lambda sensor OS2014 is a planar ZrO2 dual cell with integrated heater and is designed to measure the oxygen content value of exhaust gases.
The heater supply voltage is controlled, so the temperature of the sensor is kept at the operation point. During the water condensation phase the heater power is limited to avoid damage to the sensor’s ceramic.
Sensor OS2014 operates in combination with a special developed Oxygen Control OC2016 from Scan Tronic.
1.Cable length - 850 mm
2.Insertion length - 29 mm
3.Thread - M18 x 1,5
4.Exhaust gas pressure - 1.5 bar
Working temperature:
6.Exhaust gas pressure - max. 900 C
7.Ambient temperature - 0 - 60 C
8.Calibration interval - max. 6 months
1.The lambda sensor should be installed at a point, which permits the measurement of a representative exhaust-gas mixture, and which does not exceed the maximum permissible temperature.
2.Install at a point where the gas is as hot as possible.
3.Observe the maximum permissible temperature.
4.As far as possible install the sensor vertically.
5.The sensor is not to be fitted near to the exhaust pipe outlet, so that the influence of the outside air can be ruled out.
6.The exhaust-gas passage opposite the sensor must be free of leaks in order to avoid the effects of leak-air.
7.Protect the sensor against condensation water.